Earthing Switch vs Isolator: Differences, Relationship, and How to Use Them Together

Share to:

Earth switches and isolators both have their own importance in the electrical field. One wrong decision can lead to serious safety risks or damage to your equipment. Have you ever wondered which one to use and when? If so, don’t be confused! This blog will guide you through their differences, how they work together, and help you make the best choice for your power system. So, just keep reading!

Earth switches

1) What is an Earthing Switch?

“An earthing switch is a device that functions as safety equipment within electrical systems by offering a controlled method for unwanted electrical currents to be safely discharged into the ground.”

Its purpose is to Ground electrical circuits so that any electrical excess energy that is dangerous to the equipment or personnel is diverted or moved away safely.

When the electric system is left uncontrolled, it could cause damage to operational safety and destruction to machinery. An earthing switch works by safely “shorting” an electrical circuit for grounding during maintenance or fault conditions. Turning the switch on gives a direct path for any available or fault current to go into the earth. This prevents the danger of shocks, damage to equipment, or accidental start-up.

You may also be interested in: What is an Earthing Switch?

Key Components of the earthing switch

The earthing switch has the following components:  

a) Switching Mechanism: This is the important element by which the earthing switch can open or close and prepare the system to be grounded.

b) Contacts: Contacts are those that connect with the system and are positioned below ground level. They help disconnect the system safely by breaking the circuit connection.

c) Terminal Connections: The terminal connections permit the earthing switch to be strongly incorporated into the electric system, mainly for grounding.

Why It’s Important:

What makes an earthing switch so crucial for the safety and maintenance of electrical systems? Here are some reasons why it is important in any power system.

  • Safety: One of the main functions of the earthing switch is to protect electrical workers from the danger of electric shock. Safety is achieved by grounding the system, thus ensuring no voltages exist, which could lead to injury.
  • Preventing Equipment Damage: Parts of an electrical system are at risk of being destroyed by electrical currents, particularly when high voltages are involved. The earthing switch helps prevent this damage by safely redirecting the current.
  • Compliance: Many electrical standards require earthing switches for proper system grounding, which helps meet all safety standards.
Earthing switch Components

            Types of Earthing Switches:

So that you understand better, let’s look at the different types of earthing switches available;

i) Manual Earthing Switches:  A hand-operated switch designed for simpler and lower power systems.

ii) Automatic Earthing Switches: It worked automatically depending on system parameters for easier operation.

iii) High Voltage Earthing Switches: Such switches are crafted for use in high voltage applications, ensuring more critical systems are better safeguarded.

Earthing switches by providing proper grounding enable safe operation and maintenance of various electrical systems.

2)  What is an Isolator (Disconnector)?

“An isolator switch is an electromechanical device that is used to disconnect the power supply from a circuit.”

An isolator electrical is used to unplug an electrical device from the power source. Like switches, isolators can be operated manually. However, one basic difference is that these devices can only be operated when there is no electrical current running through the circuit.

                   Key component of an Isolator:

Each part of an isolator fulfils an important function, especially in the safety and proper operation.

a) Disconnector or Isolator Switch: A Disconnector is a specific type of device that is meant to open or close the circuit within an isolating unit, effectively shutting down the power supply to the system.

b) Electrical Connections or Joints: These establish a reliable closure or opening between the circuits.

c) Arc Chutes: Isolators in high-voltage systems come equipped with arc chutes for the suppression of any electric arc created during the opening of a switch.

Why It’s Important:

In simpler terms, the working section of the circuit must be entirely bypassed, commonly referred to as open-looped or unpowered. To be straightforward, isolators are reachable and usable when the system is completely dormant or powered down. Here’s why they are so important for an electrical system;

  • Safety: An isolator safeguards its users by isolating particular parts of an electrical system that are currently under maintenance. Isolation ensures no power is flowing into the section or circuit jumper.
  • Manual Operation: Isolators that can be manually operated are usually utilised in a non-active current status. In most cases, isolators work with circuit breaker systems that are responsible for directing current.
  • Reliability: Isolators are extremely reliable as far as damages to an electrical system are concerned. When the isolator is open, the switch shall remain switched off from the system.

 

Disconnector

                         Types of Selective Isolators:

i) Manual Isolators: These are hand-operated and used in lower voltage systems.

ii) Motorised Isolators: These can be operated from a distance and are more applicable in bigger frameworks.

iii) High-voltage isolators: These isolators are applied in cases that require high voltage. The isolators are usually placed to facilitate the safe splitting of the circuits during heavy current conditions.

Isolators, particularly those servicing high-voltage equipment, are important for the maintenance of electrical systems.

3) Key Differences Between Earthing Switch and Isolator

Both an isolator and an earthing switch serve a similar purpose and play an important part in safety provisions, but their functions and operations differ greatly. Understanding the difference between the two is crucial when making decisions related to electrical system design and maintenance. Let’s have a look at key differences:

i) Aims

  • Earthing switch: The circuit is grounded by an earthing switch to show the path to the current towards ground.
  • Isolators or disconnectors: The power supply is disconnected from a portion of the circuit, leaving only one section energised. The system is guaranteed to be completely off before commencing any maintenance works.

ii) Timing of Operation

  • Earthing switch: It is activated exclusively when the Isolator (or another circuit opening device) is opened. It cannot operate on a live circuit.
  • Isolator or disconnecter: An isolator’s operation is only permitted when the system is in the off-load condition.

iii) Earthing Switch Position in Circuit

  • Earthing Switch: It is put in the gap between the isolator and the device responsible for short-circuiting a given section of the line to the earth.
  • Isolator: Isolators are positioned between the circuit breaker and the feeder, which provides the power supply to open the circuit into separate parts to ensure safety.

iv) Safety Functions  

  • Earthing Switch: The Earthing switch keeps maintenance workers safe by removing any residual or leakage current.  
  • Isolator: Isolators prohibit energisation of the circuit but do not ground it.  

v) Visibility and interlocking  

  • Earthing Switch: Usually interlocked with Isolators to avoid locking it out when the circuit is live.  
  • Isolator: Mechanical separation is clear and hence aids safety.
            Features        Earthing switch     Isolator(Disconnector)  
Main purpose Grounding circuitIsolating circuit
Operate on De-energized vsystemOff-load only
Safety role Discharge residual current Prevents re-energization
Installed positionAfter isolatorBetween breaker and powerline

4) How They Work Together in Electrical Systems

Both earthing switches and isolators play integral roles within an electrical system. All of their components contribute toward enhanced maintainability, safety, and reliability.  

The purpose of an isolator is to completely cut off power to a specific electrical equipment or apparatus. Open isolators are used during servicing breaks to ensure that no electricity passes through the section. Even without power supplied to the equipment, some spare or residual current will always be present or available to be passed within the system.

Electrical Isolator

This can be demonstrated with the aid of the earthing switch. While an isolator removes a particular segment from the circuit, the other portion remains grounded on the earthing switch. This operator discharges any remaining or fault current into the ground. It is essential for an individual to operate the switch.

“While the isolator opens a circuit, the earthing switch grounds.”  

Coordinated Step-By-Step Instructions :

Step 1) Open the isolator and disarm the active circuit.

Step 2 ) Select the disconnected section and put it under the earthing switch.  

Step 3) Inspect without any risk.

Step 4) When all the work has been done, first clear the earthing switch.

Step 5) At the end, restore the power by opening the isolator.  

The electric safety system, along with other combinations, works together to ensure full safety in both high and low voltage systems. Such practices are common in larger industrial plants or substations. Well, you can trust these measures to guarantee the regulation or prevention of risk and enable the right functioning of the electrical system.

5) Application Examples of earthing switch and isolator

In today’s electrical systems, earthing switches and isolators play a vital role. They are utilised all over the world in different industries to enhance safety and control system operations. Here’s how ground switches and isolators are utilised:

+ Power Distribution Systems: In power grids, isolators serve to disconnect particular sections of a circuit during maintenance or in case a fault occurs. They guarantee that the line is completely isolated before attempting repair work. During this time, earthing switches are utilised to discharge any residual current remaining in the system.

+ High Voltage Substations: At substations, earthing switches disconnect the transformers, feeders, and busbars from the active system isolation. Afterwards, reserves are used to ground these areas, which might still maintain dangerous voltages due to residual energies or induced power. This is necessary before any inspection or maintenance operations.  

+ Industrial Plants: Factories equipped with heavy and automated systems utilise isolation earthing on all activities to stabilise high-power machinery. This guarantees that all charges are neutralised and personnel are not in danger.

+ Renewable Energy Plants: At solar and wind farms, isolators permit the disconnection of inverters or battery banks from the grid. Systems at great height or open fields are serviced and weather-shutdown by using a properly grounded earthing switch.

+ Switchgear Panels: Both devices are included in medium voltage and high voltage switchgear. Isolators open and control the flow of current as well as separate apparatus, while an earthing switch provides a closed grounded connection while isolating the equipment.

+ Railway Electrification Systems: An isolator is utilised to remove power from the system when working on the overhead lines in railway substations. Subsequently, earthing switches short the specific section under maintenance, safeguarding the workers from possible dangerous situations where electricity could be activated unexpectedly.

The examples highlight the collaboration of earthing switches and isolators and their functions towards protecting electrical systems. Both devices and their combined function are very flexible as they provide a wide range of solutions regardless of whether you run a power station, an industrial unit, or a renewable project.

6) Safety Considerations and Best Practices

When talking about earthing switches and isolators, safety should always come first. They must be serviced safely, and in doing so, both the individual and the equipment will not be placed in any danger.

High Voltage Earthing Switch

a) Effective and Efficient Isolation Protocols: An appropriate motor shutdown is done before any maintenance is attempted. Any work done should be done after confirming that the circuit has no power. You know, without this, live energising during maintenance will pose a great risk.

b) Safety measures for Earthing: After disconnecting the circuit, the next step is to use earthing switches to ground the opened sections. This step completes the safe discharge of any remaining or fault currents, which eliminates the risk of electric shock. Proper grounding is essential for safety practices.

Scheduled Maintenance and Checkup

Scheduled inspections are crucial to maintaining the reliability of earthing switches and isolators. For example;

  • Visual Inspection: Inspect the switch for any signs of damage, such as wear, corrosion, or deformity to the housing, terminal, and cable.
  • Manual Operation: Turn the switch physically to verify the motion of the switch, without using too much force, which could lead to jamming.
  • Value of resistance: Determine the value of resistance of the contacts of the switching device. If the resistance is high, there is corrosion that requires urgent attention.

Scheduled safety and maintenance actions maximise the chances of preventing mechanical failure while ensuring devices function when needed most. Make sure everyone who operates or maintains electrical systems is properly trained. You know, knowing how to use the earthing switches and isolators for the prescribed actions is important for safe practices.

If you are searching for top-grade and dependable earthing switches, Eberry offers an extensive selection of products specific to the safety requirements. Our catalogue includes high and medium voltage earthing switches designed to discharge residual currents safely during maintenance or fault conditions. Substations, power plants, and industrial installations can depend on safe solutions offered by Eberry , which are effective, easy to operate and durable while meeting international safety regulations.

7) Conclusion

In conclusion, the efficient operation of a power system requires knowledge of the functions of an earthing switch, isolators, and their relation to multifunction devices. Collectively, they provide protection, isolation, and maintenance, but individually, they have specific functions. The system’s dependability is increased while faults are prevented through careful selection of switches, strategising system layout, and proper maintenance.