Products

  • Home
  • Products
  • LW36 126T3150 40 High Voltage AC SF6 Tank Type Circuit Breaker 126kV GIS Breaker for Substation and Power Distribution

LW36 126T3150 40 High Voltage AC SF6 Tank Type Circuit Breaker 126kV GIS Breaker for Substation and Power Distribution

The LW36-126T High Voltage AC SF6 Tank Circuit Breaker integrates the circuit breaker and current transformer into a single unit. The arc-extinguishing chamber is horizontally mounted inside a grounded aluminum alloy housing and is paired with a CT26-type spring operating mechanism. The design features fewer components, a simple and compact layout, and a robust, durable structure, meeting the requirements for oil-free switches.

Share to:

Product Introduction

The LW36-126T High Voltage AC SF6 Tank Circuit Breaker integrates the circuit breaker and current transformer into a single unit. The arc-extinguishing chamber is horizontally mounted inside a grounded aluminum alloy housing and is paired with a CT26-type spring operating mechanism. The design features fewer components, a simple and compact layout, and a robust, durable structure, meeting the requirements for oil-free switches. With excellent mechanical properties and high reliability, all critical components are processed using CNC machining centers. The bearings used are imported international brands (e.g., IKO, INA, SKF). The mechanical life can reach up to 10,000 operations.

This circuit breaker is suitable for outdoor high-voltage switchgear in three-phase 50Hz AC systems and is used for control and protection in 72.5 (126) kV power transmission and distribution systems. It can also be used for circuit breaker connections and for switching capacitor banks.

Structural Features

The circuit breaker uses a three-phase porcelain pillar single-break structure, with a spring-operated mechanism centrally arranged and linked across the three phases, giving it an elegant and compact appearance. SF6 gas serves as both the insulating and arc-quenching medium. During operation, the three poles of the circuit breaker are interconnected with SF6 gas, and a pointer-type density relay monitors the pressure and density of the gas.

Thanks to the use of the self-energy arc-extinguishing principle and optimization of the breaker’s mechanical system design, mechanical efficiency is greatly improved, reducing operating power to a minimum. The breaker has excellent interrupting performance and a long electrical life.

The installation base and support frame are made from high-quality steel plates, with the surface treated using hot-dip galvanizing. All exposed fasteners are made from high-strength materials, with either hot-dip galvanizing or stainless steel components. The mechanism box is made from stainless steel, providing excellent corrosion resistance and high mechanical reliability for frequent operation.

With the inherent high insulating strength of SF6 gas and optimal contact movement, the breaker is capable of interrupting capacitive currents without re-ignition. The external insulation is designed with a large creepage distance (>31mm/kV), ensuring excellent resistance to contamination, allowing it to operate safely in harsh environments.

The breaker also has a strong current-carrying capacity: under a current of 1.2 times the rated value (3150A × 1.2 = 3780A), temperature rise tests show a considerable safety margin. The product’s overall appearance is compact, making on-site installation and commissioning easy with minimal maintenance required.

Main Technical Parameters of Circuit Breaker

No.Parameter NameUnitParameter Value
1Rated voltagekV126
2Rated power frequency withstand voltage (1min)
– GroundedkVK – 230
– Contact gapkVK – 265
3Rated lightning impulse withstand voltage
– GroundedkVK – 550
– Contact gapkVK – 630
4Power frequency withstand voltage of SF6 gas at zero gauge pressure (5min)HzK – 95
5Rated frequencyHz50
6Rated currentA3150
7First pole to clear factor1.5
8Rated short-circuit breaking currentkA40
9Rated short-circuit making current (peak)kA100
10Rated short-circuit withstand currentkA40
11Rated peak withstand currentkA100
12Rated short-circuit durations4
13Rated out-of-step breaking currentkA10
14Short-line fault breaking currentkA90% lk, 75% lk
15Rated line charging switching currentA31.5
16Rated operating sequenceO-0.3s-CO-180s-CO
17Main circuit resistanceμΩ≤500
18Rated SF6 gas pressure (20℃ gauge pressure)MPa0.5
19Alarm/minimum function pressure (20℃ gauge pressure)MPa0.45±0.03
20SF6 gas annual leakage rate<0.5%
21Gas moisture content (V/V)ppm≤150×10⁻⁶
22Mechanical lifeTimes10000
23Radio interference levelμV≤500
24Creepage distancemm3906/3150
25Weight of SF6 gas per unitkg15
26Weight of each circuit breakerkg2200

Leave Your Message

Related products

Request a Quote