  • LW36-40.5 Outdoor High Voltage AC SF6 Circuit Breaker Reliable Durable Electrical Protection for Power Substations

LW36-40.5 Outdoor High Voltage AC SF6 Circuit Breaker Reliable Durable Electrical Protection for Power Substations

The LW36-40.5(W)/T2000-31.5 outdoor SF6 circuit breaker is electrical equipment for a 50 Hz three-phase AC power system. It is suitable for use in power systems with a rated voltage of 40.5 kV for control and protection purposes. The internal or external current transformers can be used for measurement and protection.

Share to:

Structural Features

The LW36-40.5 SF6 circuit breaker has an outdoor porcelain post-type structure, equipped with the CT35 spring operating mechanism. The mechanism is arranged in a “T” configuration with the body, making the entire unit compact, lightweight, simple in structure, with low operating power, and easy installation and commissioning. The mechanical life is 10,000 operations, making it suitable for frequent operations. It adopts a compressed air arc-extinguishing chamber with excellent breaking performance, and its electrical life reaches 20,000 operations.

The sealing performance is reliable, with static seals using “O”-shaped sealing rings and dynamic seals using “V”-shaped sealing rings with spring pressure compensation structures. The secondary wiring board for the current transformers is produced using pressure injection molding, providing strong anti-aging performance and ensuring an annual leakage rate of <0.5%.

The installation frame and support are made from rolled steel plates, using high-strength standard components, ensuring high mechanical reliability. The internal or external current transformers use microcrystalline alloy materials with high magnetic conductivity, and the accuracy class can reach 0.2 or 0.2S. The product can be equipped with 2 to 4 current transformers per phase.

Main Technical Parameters of Circuit Breaker

No.Parameter NameUnitParameter Value
1Rated voltagekV40.5
2Rated currentA1600 / 2000
3Rated insulation levelkV95 (Grounded) / 185 (Contact gap)
4Rated short-circuit breaking currentkA25 / 31.5
5Rated out-of-step breaking currentkA7.9 / 10
6Different-phase ground fault breaking currentkA27.4 / 34.8
7Rated breaking current of single capacitor bankA400
8Rated operating sequenceO—0.3s—CO—180s—CO*
9SF6 gas rated pressure (20℃ gauge pressure)MPa0.45
10Opening time (rated voltage)ms30 ≤ t ≤ 40
11Closing time (rated voltage)ms60 ≤ t ≤ 80
12Rated short-circuit making current (peak)kA63 / 80
13Rated short circuit durations4
14Rated short-time withstand currentkA25 / 31.5
15Rated peak withstand currentkA63 / 80
16Mechanical life testTimes10,000
17Accumulated breaking times (31.5kA/40kA short-circuit)Times20
18Rated current cumulative breaking timesTimes2000
19SF6 gas annual leakage rate%≤0.5
20SF6 gas trace moisture contentppm (V/V)≤150×10⁻⁶
21External insulation leakage specific distancemm/kV≥25 / ≥31**
22Circuit breaker weightkg1000

Leave Your Message