Products

  • Home
  • Products
  • SF6 Gas Insulated Switchgear Metal Enclosed High Voltage Medium Voltage Indoor Outdoor Compact Design IEC Certified Substation Electrical Distribution Cabinet

SF6 Gas Insulated Switchgear Metal Enclosed High Voltage Medium Voltage Indoor Outdoor Compact Design IEC Certified Substation Electrical Distribution Cabinet

Share to:

Product introduction

YSR6-12/24/40.5 series of SF6 Gas Insulated Metal Enclosed switchgear (c-GlS) is independently developed by our company with sulfur hexafluoride gas as the insulating medium and can be applied in primary or secondary power distribution at a same time. lt is a new-generation medium-voltage whole-set switchgear with vacuum arc extinguishing technology, APG solid sealed technology, gas insulation technology and interface insulation technology. The product has passed the type test verification and new product technology appraisal by China’s national authoritative testing institution, The product can be widely used in various important power distribution and substation systems of China’s national economy, such as power distribution and substation network, urban power supply network, large industrial and mining enterprises, petrochemical, metallurgy, urban rail transit and so on.

The product has a modular design and can be combined according to various design schemes. The product has a sealed pressure system and all high-voltage live parts of its main circuit are sealed in the stainless steel gas tank without influence from environments. It runs reliably, is compact with little space occupied and free from maintenance.

Main Technical Parameters

ItemUnitParameter
Rated voltagekV12 24 40.5
Rated frequencyHz50
Rated currentA630/1250/2500/3150/4000/630/1250/2500
Power frequency withstand voltage (phase-to-phase and phase-to-ground)kV42 65 95
Power frequency withstand voltage (insulation breaking)kV48 79 118
Lightning impulse withstand voltage (phase-to-phase and phase-to-ground)kV75 125 185
Lightning impulse withstand voltage (insulation breaking)kV85 145 215
Rated power frequency withstand voltage of auxiliary circuitkV2
Rated instantaneous withstand currentkA25/31.5/40
Rated short-circuit periods3
Rated peak withstand currentkA63/80/100 63/80/100 50/63/80
Rated short-circuit breaking current of circuit breakerkA25/31.5/40 25/31.5/40 25/31.5
Rated short-circuit closing current of circuit breaker (peak)kA63/80/100 63/80/100 50/63/80
Rated cable charge breaking currentA25
Rated operating sequence O-0.3s-CO-3min-CO
Insulation gas SF6
Mechanical lifeTime10000
Three-position switchTime5000
Rated charge pressure (abs, 20°C)Mpa0.14
Minimum charge pressure (abs, 20°C)Mpa0.12
Sealed enclosureGradeIP67
Switch shellGradeUP4X
Annual relative leak rate of dry air%/year≤0.1
Rated power voltage of auxiliary circuitVDC48/110/220 AC220

Leave Your Message

Related products