Product Details
Rated Current:
630/1250
Rated Voltage:
12kv
Mechanical Life:
10000 Times
Rated Frequency:
50hz
Payment & Shipping Terms
Minimum Order Quantity
1 set
Packaging Details
wooden packing
Delivery Time
7 days
Payment Terms
D/A, T/T, L/C, L/C, D/P, MoneyGram, Western Union
Supply Ability
10000 pcs/month
Product Description

FKN12-12 Indoor high voltage load switch Vacuum Load Break Switch

 

Overview:

FN12-12D and FN12-12DR combination appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz for splitting load current, closed-loop current, no-load transformer and cable charging current, closing short-circuit current, fuse combination The short-circuit current can be interrupted, and the load switch equipped with the grounding switch can withstand the short-circuit current. It is mainly used in the urban substation and industrial power equipment with three-phase ring network or terminal power supply. It is used for load control and short circuit protection.

The main technical parameters:

Sr. name Unit Value
FN12-12/630 FNR12-12/100-31.5
1 Rated voltage KV 12
2 Rated frequency Hz 50
3 Rated current A 630 1250
4 Lightning impulse withstand voltage KV Ground and phase 76, isolation fracture 85
5 1min power frequency withstand voltage KV Ground and phase 42, isolation fracture 48
6 Rated thermal stable current KA 20(4s)  
7 Rated dynamic current KA 50  
8 Rated short circuit closing current (peak) KA 50 50
9 Rated short-circuit breaking current (expected value) KA   31.5
10 Rated transfer current KA   1.5
11 Breaking the capacity of the no-load transformer KVA 1250
12 Rated cable charging current A 10
13 Mechanical life times 4000
14 The fuse triggers the load switch opening time S   <0.06
15 Grounding switch thermal stability current KA 20(2s)  
16 Grounding switch dynamic steady current (peak) KA 50  
17 Control loop supply voltage   AC DC 110,220