FZN25-12DL/T200-31.5 11kv 33kV direct deal top sale Indoor high voltage load break switch 12kv with earthing
Overview:
FN12-12D and FN12-12DR combination appliances are three-phase high-voltage switchgear with rated voltage of 12KV and rated frequency of 50Hz for splitting load current, closed-loop current, no-load transformer and cable charging current, closing short-circuit current, fuse combination The short-circuit current can be interrupted, and the load switch equipped with the grounding switch can withstand the short-circuit current. It is mainly used in the urban substation and industrial power equipment with three-phase ring network or terminal power supply. It is used for load control and short circuit protection.
The main technical parameters:
Sr. | name | Unit | Value | ||
FN12-12/630 | FNR12-12/100-31.5 | ||||
1 | Rated voltage | KV | 12 | ||
2 | Rated frequency | Hz | 50 | ||
3 | Rated current | A | 630 | 125 | |
4 | Lightning impulse withstand voltage | KV | Ground and phase 76, isolation fracture 85 | ||
5 | 1min power frequency withstand voltage | KV | Ground and phase 42, isolation fracture 48 | ||
6 | Rated thermal stable current | KA | 20(4s) | ||
7 | Rated dynamic current | KA | 50 | ||
8 | Rated short circuit closing current (peak) | KA | 50 | 50 | |
9 | Rated short-circuit breaking current (expected value) | KA | 31.5 | ||
10 | Rated transfer current | KA | 1.5 | ||
11 | Breaking the capacity of the no-load transformer | KVA | 1250 | ||
12 | Rated cable charging current | A | 10 | ||
13 | Mechanical life | times | 4000 | ||
14 | The fuse triggers the load switch opening time | S | <0.06 | ||
15 | Grounding switch thermal stability current | KA | 20(2s) | ||
16 | Grounding switch dynamic steady current (peak) | KA | 50 | ||
17 | Control loop supply voltage | AC DC 110,220 |