Place of Origin:
Zhejiang, China
Brand Name:
Eberry
Certification:
CE,CQC,ISO9001
Model Number:
FL(R)N36(12 40.5kV)
Contact Us
FL(R)N36(12 40.5kV) Sulphur hexafluoride(SF6) high-voltage load switch is a switchgear with a rated voltage of 12-40.5kV, with SF6 gas as the arc-extinguishing and insulating medium, as well as the three work positions such as closing, breaking and grounding; it has the features such as compact, easy to install and use and highly adaptable to environments.
This series of load switch is divided into FL(R)N36(12-40.5kV) (K type single spring operating mechanism) and FL(R)N36(12-40.5kV) (K type single spring operating mechanism), which are of different sizes and with different operating modes.
This series of load switches are divided into FL(R)N36(12-40.5kV) (K type single-spring actuator) and FL(R)N36(12-40.5kV) (A type double-spring actuator). FL(R)N36(12-40.5kV) can compose load switch + fuse combined appliance pit with control and protection function for protection and control of electrical power equipment in power supply and substation, is specially ideal for ring main units, cable junction boxes and power distributors.
It meets these standards such as IEC60265, IEC62271, GB3804, GB16926, etc.
NO | Item | Units | Technical parameters | ||
1 | Rated voltage | kV | 12 | ||
2 |
Rated frequency |
Hz | 50/60 | ||
3 |
Rated current |
A | 630 | ||
5 |
1min power frequency withstand voltage, phase-to-ground, phase-to-phase/breaking |
kV | 42/48 | ||
6 |
Lightning impact withstand voltage (peak), phase-to-ground, phase-to-phase/breaking |
kV | 75/85 | ||
7 |
Main circuit Rated thermal stabilized current |
kA/3s | 20 | ||
8 |
Grounding circuit Rated thermal stabilized current |
kA/2s | 20 | ||
9 |
Rated dynamic stabilized current (peak) |
kA | 50 | ||
10 |
Rated short-circuit closing current |
kA | 50 | ||
11 |
Rated closed loop breaking current |
A | 630 | ||
12 |
Rated active load breaking current |
A | 630 | ||
13 |
Rated cable charge breaking current |
A | 10 | ||
14 |
Rated short-circuit breaking current |
kA | 20 | ||
15 |
Rated transfer current |
A | 1750 | ||
16 |
Mechanical life Load switch/grounding switch |
Time | 3000/2000 | ||
17 |
SF6 gas pressure (relative pressure at 20°C) |
Mpa | 0.045 |