Send Message
Home > products > Outdoor Vacuum Circuit Breaker >
ZW32 40.5KV Outdoor Vacuum Circuit Breaker MV HV VCB With Disconnector

ZW32 40.5KV Outdoor Vacuum Circuit Breaker MV HV VCB With Disconnector

40.5KV Outdoor Vacuum Circuit Breaker

ZW32 Outdoor Vacuum Circuit Breaker

HV mv vacuum circuit breaker

Place of Origin:

China

Brand Name:

EBERRY

Certification:

CE,CQC,ISO9001

Model Number:

ZW32-40.5

Contact Us

Request A Quote
Product Details
Rated Voltage:
40.5KV
Rated Current:
630/1250/1600/2000/2500
Mechanical Life:
M2 Level
Customization:
Yes
Type:
Ourdoor
Waterproof:
IP65
Payment & Shipping Terms
Minimum Order Quantity
1 set
Packaging Details
plywood Carton
Delivery Time
5-10 days
Payment Terms
L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability
10000 pcs/month
Product Description

ZW32-40.5KV Out Door MV HV VCB with disconnector Outdoor Vacuum Circuit Breaker

 

ZW32-40.5 outdoor high-voltage alternating-current vacuum circuit breaker is a new outdoor high-voltage alternating-current switchgear of our vacuum circuit breaker series. Its rated voltage is 40.5kV. It applies to places with such voltage level, including overhead lines, industria and mining enterprises, power stations, substations, etc. Under its normal operating conditions and specified technical parameters, it can the system protection requirements of the grid. It is charaterized by automatic re-making, stble operation and long elecric life.

Technical Parameter

1.1 Technical parameters

ltem Unit Reference value
Rated voltage kV 40.5
Rated insulation level Lightning impulse withstand voltage kV 185
1min power- frequency withstand voltage kV 95
Rated frequency Hz 50/60
Rated current A 630/1250/1600/2000/2500
Rated short-circuit breaking current kA 20/25/31.5
Rated short-circuic making current (peak value) kA 50/63/80
Rated short-time withstand current kA 20/25/31.5
Rated withstand current (peak value) kA 50/63/80
Rated operation sequence   O-0.3s-CO-180s-CO
Rated short-circuit duration s 4
Times of making-breaking with the rated short-circuit current Times 30
Mechanical life   M2 level
Weight kg 280

 

Standard

1.IEC 62271-100 High-voltage switchgear and controlgear

2.GB/T 11022 -2011 Common specifications for high-voltage switchgear and controlgear standards

3.GB 1984 High-voltage alternating-current circuit-breakers

4.GB311.1 Insulation co-ordination for high voltage transmission and distribution equipment

Ambient condition

1. Altitude: ≤ 2000m

2. Ambient temperature: -40°C~+40°C

3. Relative humidity:≤95% (daily average) or≤90% (monthly average)

4. Ambient pllution: IV

5.Wind speed:≤34m/s (equivalent to a pressure of 700pa on a cylindrical surface) .

 

ZW32 40.5KV Outdoor Vacuum Circuit Breaker MV HV VCB With Disconnector 0ZW32 40.5KV Outdoor Vacuum Circuit Breaker MV HV VCB With Disconnector 1ZW32 40.5KV Outdoor Vacuum Circuit Breaker MV HV VCB With Disconnector 2

 

 

Send your inquiry directly to us

Privacy Policy China Good Quality VCB Vacuum Circuit Breaker Supplier. Copyright © 2023-2024 vcbbreaker.com . All Rights Reserved.